15
Controllo per i-32V5 MIDI Air/water inverter chillers and heat pumps with axial fans
• The compressor shutdown is set by the parameter b05: the compressor shutdown when Tw,out < Tw,out,set - b05
• The compressor restart when : se , the compressors restart when the discharge
probe temperature is lower than the setpoint 10°C:
REGULATION IN HEAT MODE
• Tw,out,set = seng setpoint in heat mode
• = Tw,out,set – Tw,in,set
• b05 = compressor regulaon delta cut-o = 0,2°C (default)
• b25 = compressor regulaon delta cut-on= 2°C
RPM
Tw,out (outlet water temp.)
Tw,out,set
HzMin
• The compressor shutdown is regulated by parameter b05: the compressor shutdown when
• The compressor restart when
EXCEPTION: if , the compressors restart when the discharge probe temperature is lower than the setpoint 10°C:
10. FAN
The unit's fan is controlled depending on the operaon of the compressor. Venlaon is controlled according to the condensing pressure in
cooling mode or according to the evaporang pressure in heang mode. Pre-venlaon takes place every me the compressor is switched on
and o.
SILENCED VENTILATION
Conguring a digital input DI9 with parameter H53=25 it is possible to manage the funcon of silent venlaon management.
Parameter VALUE
H53
0 (default) Funcon disabled
25
Open contact -> standard mode
Close contact -> silenced mode
With the funcon acve, the noise, output and power of the unit are limited, for addional informaon see the installer user manual.
11. COMPRESSOR CRANKCASE RESISTENCE
The crankcase resistence is acvated if the compressor has been o for at least 30 minutes and if the temperature measured by the discharge
probe is below 20 °C (with a hysteresis of 2.0 °C). When the compressor restarts, the crankcase resisitence is disabled.
12. ENABLING DOMESTIC HOT WATER PRODUCTION
To enable the producon of domesc hot water it is necessary to connect a probe to the analogue input ST6 to be posioned inside the tank (the
relave terminals are indicated in chapter 5 or on the electrical diagram). Once the DHW temperature probe has been posioned and connected,
it must be enabled by seng parameter H17 = 6.
The DHW valve must be connected to digital output DO6 (see Chapter 5), and the relave control must also be enabled with parameter H84 =
6 (default).
The domesc hot water (DHW) funcon is controlled through parameter H10:
Parameter VALUE
H17 6 DHW temperature probe
H84 6 DHW valve control