Controllo per i-32V5 MIDI Air/water inverter chillers and heat pumps with axial fans
24
In this way the heat pump will stop at the set point and the thermal jump, according to the set oset, will be borne by the boiler and/or the
integraon resistors.
19.
In units with KA accessory, this funcon is acve from the factory conguraon. The kit consists of an anfreeze heater posioned on the ex-
changer on the system side and a heang cable placed on the base of the unit. The installer can modify the operaon of the anfreeze resistors
by accessing the relave parameter menu:
PRG -> PSS -> PRG -> (enter installer password) -> PRG -> PAr -> PRG -> Fro
In heang mode, the water anfreeze heater is acvated when the ow water temperature falls below r02 (default r02 = 4,0°C), it is switched
o when the temperature measured by the outlet water probe exceeds °C.
If the unit is in OFF or cooling mode, the water anfreeze heater is acvated when the ow water temperature falls below r03 (default r03 =
4,0°C), it switches o when the temperature measured by the outlet water probe exceeds °C.
The crankcase heater, on the other hand, switches on when the outside air temperature falls below 3°C and switches o when the outside tem-
perature exceeds 5°C.
20.
This opon allows to produce free hot water through paral heat recovery by desuperheang the gas from the compressor outlet. Units with
DS accessory are equipped with a control expansion board, which allows the connecon of a water temperature probe for DS to acvate the call
for recovery.
To enable operaon, the following parameters must be set and the DS water temperature probe must be connected to terminal XC-121.1/12.2:
Parameter VALUE TERMINAL
rE01 1 DS enabled in chiller mode
H17 6 XC-121.1/12.2 DS water temperature sensor
Recovery is enabled for operaon if all the following condions are met:
• Compressor in operaon
• Defrosng is not in progress and is not counng to enter defrost mode.
• There are no safety controls or restricons acve
The recovery call is acvated if the temperature detected by the probe falls below the setpoint °C and is deacvated when the tem-
perature exceeds the setpoint San.
For more informaon see the technical bullen of the unit.
-
ress.
21.
If the System Management kit (oponal) is present, a second control is located inside the electrical panel that acts as an I/O resource expansion
module. With this second control it is possible to increase the number of logics that can be managed by the main control; in parcular, these
logics are used for system management and are listed below:
Parameter VALUE
H86 9 Compressor operaon signalling
H87 24 Alarm signalling
H88 47 Machine block signalling
H89 31 *Plant season signalling
H90 21 *Defrosng in progress signalling
(*) only for heat pump units
22. PERMITTED CONFIGURATION TABLES
Below is a table of user and installer parameters including all the permied conguraons. Not all the conguraons listed can be selected at the
same me. The values listed below may be subject to updates, in case of doubt please contact the company.
CAUTION:
this manual.