29
Controllo per i-32V5 MIDI Air/water inverter chillers and heat pumps with axial fans
Alarm code DESCRIPTION
E042 Insucient heat exchange alarm Macchine/Sanitary
E050 High DHW tank temperature alarm -
E611 Water inlet probe failure Machine
E621 Water outlet probe failure Machine
E631 Compressor sucon probe failure Machine
E641 Compressor discharge probe failure / high pressure switch intervenon Machine
E651 External air / fan thermal probe failure Machine
E661 DHW probe failure (ST6) Machine
E671 Fault in remote plant probe (ST7) Machine
E691 Low pressure transducer failure Machine
E701 High pressure transducer failure Machine
E711 Fault in voltage input 0-10V DC Machine
E801 Inverter communicaon meout Compressor
E851 Inverter hardware problem Compressor
E861 Motor current too high Compressor
E871 High inverter heatsink temperature Compressor
E881 Supply voltage out of limits (DC bus) Compressor
E891 Compressor not connected Compressor
E901 Wrong compressor model Compressor
E911 Overload protecon Compressor
E921 PFC/POE overcurrent Compressor
E931 Internal communicaon error Compressor
E941 PFC fault Compressor
E951 Heatsink and/or ambient temperature sensor fault Compressor
E961 Abnormal condion Compressor
E971 EEPROM error Compressor
24. MODBUS VARIABLES
The control has the following modbus conguraon by default:
• Baud rate: 9600
• Parità: EVEN
• Data bit: 8
• Stop bit: 1
• Device ID: 1
To congure the Modbus communicaon according to your requirements, you must modify the following parameters:
Parameter VALUE
H124
0 Baud rate 4800 bit/s
1 Baud rate 9600 bit/s
2 Baud rate 19200 bit/s
3 Baud rate 38400 bit/s
H125
0 Parity NONE e stop bit 2
1 Parity ODD e stop bit 1
2 Parity EVEN e stop bit 1
3 Parity NONE e stop bit 1
H126 1 ÷ 120 Serial address (Device ID)
The following table lists the Modbus registers of the control:
Format Bit R/W Name Note
1 INT - R -
Data version
Firmaware version
2 INT - R - Firmware release
3
BYTE (H) - R - Firmware sub-release
BYTE (L) - R - Firmware creaon day
4
BYTE (H) - R - Firmaware creaon month
BYTE (L) - R - Firmware creaon year
10 BOOL
0 R -
Digital inputs
ID1 (ow swich)
1 ID 2 If acve
2 ID 3 (on/o) Acve by default