Controllo per i-32V5 MIDI Air/water inverter chillers and heat pumps with axial fans
Format Bit R/W Name Note
951 BOOL
1
R -
ALARM - E18 High temperature
9 ALARM - E26 * Thermal pump 2
11 ALARM - E41 Incongruent temperatures
12 ALARM - E42 Insucient heat exchange
13 ALARM - E50
high temperature domesc hot wa-
ter storage tank
14 ALARM - E101 Gi module disconnected
952 BOOL
0
R -
ALARM - E611 Inlet water probe
1 ALARM - E621 Outlet water probe
2 ALARM - E631 Intake temperature
3 ALARM - E641 Exhaust temperature
4 ALARM - E651 Outside temperature
5 ALARM - E661 Probe 6 If acve
6 ALARM - E671 Probe 7 If acve
7 ALARM - E681 Probe 8 If acve
8 ALARM - E691 low pressure transducer
9 ALARM - E701 high pressure transducer
10 ALARM - E711 Probe 11 If acve
11 ALARM - E612 *module Gi - Probe 1 If acve
12 ALARM - E622 *module Gi -Probe 2 If acve
13 ALARM - E632 *module Gi - Probe 3 If acve
14 ALARM - E642 *module Gi - Probe 4 If acve
15 ALARM - E652 *module Gi - Probe 5 If acve
953 BOOL
0
R -
ALARM - E662 *module Gi - Probe 6 If acve
1 ALARM - E672 *module Gi - Probe 7 If acve
2 ALARM - E682 *module Gi - Probe 8 If acve
3 ALARM - E692 *module Gi - Probe 9 If acve
4 ALARM - E702 *module Gi - Probe 10 If acve
5 ALARM - E712 *module Gi - Probe 11 If acve
954 BOOL
1
R -
ALARM- E801 Inverter link 1
2 ALARM - E802 *Inverter link 2
4 ALARM - E851 Hardware fault inverter 1
5 ALARM - E852 *Hardware fault inverter 2
7 ALARM - E861 Overcurrent inverter 1
8 ALARM - E862 High temperature inverter 1
10 ALARM - E871 Bad voltage inverter 1
11 ALARM - E872 *High temperature inverter 2
13 ALARM - E881 Bad voltage inverter 1
14 ALARM - E882 *Bad voltage inverter 2
955 BOOL
0
R -
ALARM - E891 Phase sequence inverter 1
1 ALARM - E892 *Phase sequence inverter 2
3 ALARM - E901 Model error inverter 1
4 ALARM - E902 *Model error inverter 2
6 ALARM - E911 Overload error inverter 1
7 ALARM - E912 *Overload error inverter 2
9 ALARM.- E921 Overcurrent PFC inverter 1
10 ALARM - E922 *Overcurrent PFC inverter 2
12 ALARM - E931
Internal communicaon error invert-
er 1
13 ALARM - E932
*Internal communicaon error
inverter 2
15 ALARM - E941 Fault PFC inverter 1
956 BOOL
0
R -
ALARM - E942 *Fault PFC inverter 2
2 ALARM - E951 Probe error inverter 1
3 ALARM - E952 *Probe error inverter 2
5 ALARM - E961 Abnormal condion inverter 1
6 ALARM - E962 *Abnormal condion inverter 2
8 ALARM - E971 EEPROM inverter 1
9 ALARM - E972 *EEPROM inverter 2
(*) if present