Electrical Installation
Status Indicators
IDX 70 User Manual
mmag | 2022-04 | rel10520
4-43
4.4.1 NET Status
The LED displays the actual status and possible errors of the IDX in respect to the NET network:
Green LED shows the RUN state
Red LED indicates errors
Table 4-34 NET status LEDs
4.4.2 Device Status
The LED displays the actual status and possible errors of the IDX:
Green LED shows the status
Red LED indicates errors
Table 4-35 Device status LEDs
LED
Description
Green Red
OFF IDX is in state INIT
Blink IDX is in state PRE-OPERATIONAL
Single flash IDX is in state SAFE-OPERATIONAL
ON IDX is in state OPERATIONAL
Flicker IDX is in state BOOTSTRAP
OFF IDX is in operating condition
Double flash
An application watchdog timeout has occurred
Example: Timeout of Sync Manager Watchdog
Single flash
IDX has changed the COM state due to an internal error
Example: Change of state “Op” to “SafeOpError” due to Sync Error
Blink
General Configuration Error
Example: State change commanded by master is not possible due to
actual settings (register, object, hardware configuration)
Blink = continuous blinking (2.5 Hz)
Flicker = continuous flickering (10 Hz)
Flash = flashing (0.2 s), followed by pause of 1 s
LED
Description
Green Red
Slow OFF
Power stage is disabled. The IDX is in status…
“Switch ON Disabled”
“Ready to Switch ON”
“Switched ON”
ON OFF
Power stage is enabled. The IDX is in status…
“Operation Enable”
“Quick Stop Active”
OFF ON
FAULT state. The IDX is in status…
•“Fault
ON ON
Power stage is enabled. The IDX is in temporary status…
“Fault Reaction Active”
Flash ON No valid firmware or firmware download in progress
Flash = flashing (0.9 s OFF/0.1 s ON) Slow = slow blinking (1Hz)