58 AGZ 010B through 034B IOMM AGZB1
SET UNIT SPs (14)
ENTER PASSWORD XXXX
Active Password
Level:None
Two four-digit passwords provide OPERATOR and MANAGER levels of access to
changeable parameters. The passwords are preprogrammed into the controller. The
Operator Password is 0100. Either password must be entered using the ENTER
PASSWORD (12) screen before a protected setting can be changed.
This screen can be accessed either through the SET OTHER menu or by simply pressing
the ENTER key while on one of the SET screens. The controller will automatically go
from the screen with the setting change to this screen. After the correct password has been
entered, the controller will automatically return to the original set screen.
Once a password has been entered, it remains valid for 15 minutes after the last key-press.
SET COMP SPs
SET COMP SPs (1)
Clear Cycle Tmr=No
Stop-Start =XXmin
Start-Start =XXmin
This menu sets the anti-recycle timers. Stop-Start is the time required before starting a
compressor after it has stopped. Start-Start is the time required before starting a
compressor after the last time it has started. It recommended that these default values not
be changed.
SET COMP SPs (2)
InterStageUp=XXXsec
InterStageDn=XXXsec
InterStageUp is the time delay since the last stage change before a compressor can stage on.
InterStageDn is the time delay since the last stage change before a compressor can stage off
normally (not by an alarm).
SET COMP SPs (3)
Compressor 1=Enable
Compressor 2=Enable
ALARM SETPOINTS
SET ALARM LMTS (1)
LowEvPr
Hold=XXXpsi
Unload=XXXpsi