EasyManua.ls Logo

Megger Three-Phase TTR - Figure 4-1. Setup for Testing Single-Phase Transformer; Figure 4-2. Setup for Testing Single-Phase Autotransformer

Megger Three-Phase TTR
70 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
M
AVTMTTR330 Rev 3 March 2010
12
2. Connect the H and X test cables to the respective H and X receptacles of the
TTR330. Make sure that the connectors are securely fastened (using
clockwise rotation) to the receptacles.
3. Connect the heavy-duty clamps marked H1 and H2 of the test lead to the
corresponding (high-voltage winding) terminals of the transformer under
test. Figures 4-1 and 4-2 show test setups for single-phase transformers.
Figures 4-3 and 4-4 show test setups for regulators.
4. Connect the heavy-duty clamps marked X1 and X2 of the test lead to the
corresponding (low-voltage winding) terminals of the transformer under test.
Figures 4-1 and 4-2 show test setups for single-phase transformers. Figures
4-3 and 4-4 show test setups for regulators.
5. On/OFF Switch. It is only after all of the above connections are safely made
and all safety precautions of sections 2 and 3 are satisfied, should the
On/OFF switch be turned to the ON position.
Figure 4-1. Setup for Testing Single-Phase Transformer
Figure 4-2. Setup for Testing Single-Phase Autotransformer
To test windings other than H1 – H2 and X1 – X2, ensure that the heavy-duty
clamp marked H1 is connected to the lower numbered terminal and H2 to the

Table of Contents

Related product manuals