EasyManua.ls Logo

Megger Three-Phase TTR - Three-Phase, Three-Winding Transformers; Table 4-2. Test Lead Markings for Three-Phase Transformers

Megger Three-Phase TTR
70 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connecting to the Transformer
AVTMTTR330 Rev 3 March 2010
15
5. On/OFF Switch. It is only after all of the above connections are safely
made and all safety precautions of sections 2 and 3 are satisfied, should the
On/OFF switch be turned to the ON position.
Table 4-2. Test Lead Markings for Three-Phase Transformers
Test Lead Marking Transformer Heavy-Duty
Clamp
Test Lead
ANSI
CEI/IEC Australian Terminal Voltage Boot Color Color Band
H0 1N N Neutral Red White
H1 1U A
2
/A
4
High Red Red
H2 1V B
2
/B
4
High Red Yellow
H3 1W C
2
/C
4
High Red Blue
X0 2N N Neutral Black White
X1 2U a
1
/a
2
/a
4
Low Black Red
X2 2V b
1
/b
2
/b
4
Low Black Yellow
X3 2W c
1
/c
2
/c
4
Low Black Blue
Note: According to Australian standard, wye and delta transformer winding
connections have a numerical suffix of 1 and 2. The zigzag transformers
have a numerical suffix of 4.
Three-Phase, Three-Winding Transformers
This type of transformers has primary, secondary, and tertiary windings. Primary
and secondary windings are tested as a regular three-phase, two-winding
transformer. To test tertiary winding, perform the following setup procedure:
1. With the ON/OFF Switch in the OFF position, make the circuit
connections as described in Section 3.
2. Connect the H and X test cables to the respective H and X receptacles of the
TTR330. Make sure that the connectors are securely fastened (using
clockwise rotation) to the receptacles.
3. Connect the heavy-duty clamps marked H0, H1, H2, and H3 of the test lead
to the corresponding terminals of the transformer under test. Refer to Table
4-2 for test lead markings. With delta connected windings, H0 is not used.
With wye connected windings, a neutral connection for H0 is normally
available
4. Connect the heavy-duty clamps marked X0, X1, X2 , and X3 of the test lead
to the corresponding tertiary (low-voltage winding) terminals (Y0, Y1, Y2,

Table of Contents

Related product manuals