109
ature
protection
point
ture
protection
point
P97.07
Over-voltag
e stall
selection
Over-voltage
stall selection
0: Disabled (when the braking
resistor is installed)
1: Enabled
1 1 × √ ×
P97.08
Over-voltag
e point at
stall
Over-voltage
point at stall
120.0%~150.0%Udce
0.1%
140.0%
× √ ×
P97.09
Auto current
limiting
action
selection
Auto current
limiting
action
0: Disabled at constant speed
1: Enabled at constant speed
Note: Always enabled for
acceleration/deceleration
1 1 × √ ×
P97.10
Auto current
limiting level
Current
limiting level
20.0%~200.0%Ie 0.1%
G: 150.0%
P: 110.0%
× √ ×
P97.11
Frequency
reduction
rate upon
current
limiting
Frequency
reduction
rate
0.00~99.99Hz/s 0.01Hz/s
10.00
Hz/s
× √ ○
P97.12
Grounding
short circuit
detection
upon
power-up
Grounding
short circuit
detection
upon
power-up
0: Disable
1: Enable (enabled for model of
7.5kW and below)
1 1 × √ ○
P97.13
Auto reset
times
Auto reset
times
0: No function
1~100: Auto reset times
Note: Auto reset is not available
for module protection, external
device fault and AI over-current
fault
1 0 × √ ×
P97.14
Auto reset
interval
Reset
interval
2.0~20.0s per time 0.1s 5.0s × √ ×
P97.15
The first
fault type
First new
fault
0: No abnormal record
1: Over-current during the drive
acceleration (Er.oC1)
2: Over-current during the drive
deceleration (Er.oC2)
3: Over-current when the drive is
running with constant speed
(Er.oC3)
4: Over-voltage during the drive
acceleration (Er.oU1)
5: Over-voltage during the drive
deceleration (Er.oU2)
6: Over-voltage when the drive is
running with constant speed
(Er.oU3)
1 0 × √ *