61 
 
Fig. 4-7    Operation example for setting the set frequency   
4.1.3.6 Switching status display parameters 
The drive parameters displayed on the operation panel when the drive is stopped can be set through function 
code P16.02, such as the frequency, bus voltage, etc. (For details, please refer to the description of function 
codes of Group P16). These status parameters can be viewed by pressing the 
  key on the operation 
panel when they have been set. The example for the status parameter display in the drive stop status when 
P16.02 is FFF is as shown in Fig.4-8.   
 
Fig. 4-8    Operation example for switching status parameter display   
4.2 Drive running mode   
The terms describing the drive control, running and status will appear in the following chapters. Please read 
carefully this chapter. It will help you understand and properly use the functions described in the following 
chapters.  
4.2.1 Drive running command channel   
The drive running command channel refers to the physical channel for the drive to receive the running 
command: start, stop, jog, etc. There are four types of running command channels:   
1. Operation panel: To control through the RUN, STOP and M (when set as the JOG function) keys on the 
operation panel. 
2. Control terminal: To control through the control terminals X1, X2 (default, other digital input terminals 
can be set as FWD and REV input control terminals as well), COM (two-wire system) and Xi (three-wire 
system).  
3. Serial port: To control the start and stop through the host device.   
4. Field bus: To control the start and stop through the field bus (Profibus-DP, CanOpen, etc.).   
50.00  0.0  1500.0
0.50
 
540 
0.00
0.0 
0.00
0.00 
 
 
 
 
 
 
 
50.00  P00.00 P00.00
P02.0550.00
> 
 
MENU 
ESC 
MENU 
ESC 
ENTER
DATA
> 
P02.00
P02.00
25.00
> 
P00.06
25.00 
ENTER
DATA