6.12 Advanced function parameters (Group P12)
0: Disabled
1: Enabled
In the no-load or light load process of the motor, detect the load current and properly adjust output
voltage to achieve energy-saving effect.
Note
This function is especially suitable for the fan and pump load.
Table 6-15 Set the carrier wave frequency when the drive is outputting the PWM wave
Drive power
Leave-factory value of carrier wave
frequency
G: 0.75
7.5 kW
P: 0.75
7.5 kW
6kHz
G: 11
45 kW
P: 11
55 kW
4kHz
G: 55
90 kW
P: 75
110 kW
3kHz
G: 110
280 kW
P: 132
315 kW
2kHz
Note
1. The carrier wave frequency can affect noise during the motor running, generally, it can be set as 3~5kHz.
For the occasion when the quiet running is required, the carrier wave frequency can be generally set as
6~8kHz.
2. When the drive is running with the carrier wave frequency above the leave-factory setting value, the drive
needs to derate 5% of the power to run for every increase of 1kHz.
3. In the vector control mode, the minimum for the setting range of the carrier wave frequency is 2kHz.
PWM mode o
p
timization 0000~1111H
(
1001
)
P12.03
Carrier f
r
e
q
uenc
y
0.7~15.0kHz
(
4.0
)
P12.02
Ener
gy
-savin
g
runnin
g
0~1
(
0
)
P12.01
Reserved 0P12.00