9 
R4 
MV300P-4T11 17.0  26.0  25.0  11 
MV300P-4T15 21.0  35.0  32.0  15 
MV300P-4T18.5 24.0  38.5  37.0  18.5 
R5 
MV300P-4T22 30.0  46.5  45.0  22 
MV300P-4T30 40.0  62.0  60.0  30 
MV300P-4T37 50.0  76.0  75.0  37 
R6 
MV300P-4T45 60.0  92.0  90.0  45 
MV300P-4T55 72.0 113.0  110.0  55 
R7 
MV300P-4T75 100.0 157.0  152.0  75 
MV300P-4T90 116.0 180.0  176.0  90 
R8 
MV300P-4T110 138.0  214.0  210.0  110 
MV300P-4T132 167.0  256.0  253.0  132 
R9 
MV300P-4T160 200.0  307.0  304.0  160 
MV300P-4T200 250.0  385.0  380.0  200 
R9P   MV300P-4T220  280.0  430.0  426.0  220 
R10 
MV300P-4T280 355.0  525.0  495.0  280 
MV300P-4T315 445.0  590.0  585.0  315 
R11 
MV300P-4T355 500.0  665.0  650.0  355 
MV300P-4T400 565.0  785.0  725.0  400 
 
1.4   Technical specifications of product   
Table 1-3     Technical specifications of drive   
Input power 
Rated voltage (V) 
Three-phase: 380V~480V; continuous fluctuation of voltage: 
±10%, transient fluctuation of voltage: -15%~+10% (i.e. the 
range is 323V~528V); Voltage unbalance rate:  <3%, the 
distortion rate complying with IEC61800-2   
Rated input current (A)  Please refer to Table 1-1 and Table 1-2.   
Rated frequency (Hz)      50Hz/60Hz, fluctuation range: ±5% 
Output power 
Standard applicative motor (kW) 
Please refer to Table 1-1 and Table 1-2.   
Rated capacity (kVA) 
Rated current (A) 
Output voltage (V) 
Output with three-phase under rated input conditions: 0 ~ rated 
input voltage, the error is less than ±3% 
Output frequency (Hz)  V/F: 0.00~3000.0Hz (unit: 0.01Hz); vector control: 0~650.00Hz 
Overload capacity   
G: 1 min for 150% rated current, 0.5 s for 200% rated current   
P: 1 min for 110% rated current, 1 s for 150% rated current   
Operation control 
features 
Control mode  Vector control without PG, V/F control without PG 
Maximum output frequency  3000Hz for V/F control, 650Hz for vector control 
Speed adjusting range    1: 200 (vector control without PG)