164
When 0 is selected for the BIT, it indicates the positive logic. When 1 is selected, it indicates the negative
logic.
For example:
If you want to set X1~X4 as positive logic and set X5~X6 as negative logic, make the following setting:
Set the logic state of X4~X1 as 0000, the corresponding hexadecimal value as 0, and then the LED will
display 0 at the unit place. Set the logic state of X6~X5 as 11, the corresponding hexadecimal value as 3,
and then the LED will display 3 at the tens place.
This function code is used to set the enabled state of the host device virtual input terminal. For the
detailed setting method, please refer to the description of P09.15.
0: Common open collector output
1: High-speed pulse output
Y2 and the relay terminal can be defined as the multi-functional digital output; in addition, Y1 can also be
used as the high-speed pulse output (0~50kHz) terminal. When Y1 terminal is used as the high-speed
pulse output terminal, please refer to relevant functions of P09.29.
Table of function definition of the multi-functional digital output:
Table 6-12 Function definition of the multi-functional digital output
Item Function Item Function
0
Drive in running state signal
(RUN)
1 Frequency arrival signal (FAR)
2 Speed non-zero signal 3
Frequency level detection signal
(FDT1)
4
Frequency level detection signal
(FDT2)
5 Overload detection signal (OL)
6 Lockout for undervoltage (LU) 7 External fault stop (EXT)
8 Frequency upper limit (FHL) 9 Frequency lower limit (FLL)
10 Drive running at zero-speed 11
Simple PLC stage running
completion indication
12 PLC cycle completion indication 13 Reserved
14 Reserved 15 Drive ready for running (RDY)
16 Drive fault 17 Host device switch signal
18 Reserved 19 Limiting torque
20 Flux detection signal 21 Reserved
22 Analog torque offset enabled 23 Over-torque output
Reserved 0P09.21
Relay RO1 output function selection 0~44 (15)P09.20
Open collector output terminal Y2 0~44 (1)P09.19
Open collector output terminal Y1 0~44 (0)P09.18
Output selection of Y1 0~1 (0)P09.17
Virtual input terminal setting 00
~
3FH (00)P09.16