177
10V~0:0
)20mA~0(or
10V~2:1
)20mA~4(or
Fig. 6-48 Analog output type selection
This function code is used for selecting the analog output range of AO1. For the voltage or current output,
it shall be determined by the jumper on the terminal board. For details, please refer to the description of
the terminal board.
The linear correspondence relationship between the AO1 output and the indication range is as shown in
Table 6-14.
Table 6-14 Analog output terminal indication
Item Function Indication range
0 Output frequency 0~Maximum output frequency
1 Set frequency 0~Maximum output frequency
2
Set frequency (after acceleration/
deceleration)
0~Maximum output frequency
3
Rotating speed of motor (V/F
control disabled)
0~Maximum rotating speed
4 Output current 0 ~ 200% of the rated current of the drive
5 Output current 0 ~ 200% of the rated current of the motor
6 Output torque 0 ~ 300% of the rated torque of the motor
7 Output torque current 0 ~ 300% of the rated torque of the motor
8 Output voltage 0 ~ 120% of the rated voltage of the drive
9 Bus voltage 0~800V
10 AI1 0~Maximum analog input
11 AI2 0~Maximum analog input
12 Reserved
13 Output power 0 ~ 200% of the rated power of the motor
14 Percentage of host device 0~4095
15 Torque limit value 1 0 ~ 300% of the rated torque of the motor
16 Torque limit value 2 0 ~ 300% of the rated torque of the motor
17 Torque offset 0 ~ 300% of the rated torque of the motor
18 Torque command 0 ~ 300% of the rated torque of the motor
19 Flux command 0 ~ 100% of the rated flux of the motor
AO1zero offset correction -100.0%~100.0%
0.0%
P10.25
AO1
ain 0.0~200.0%
100.0%
P10.24
Analo
out
ut terminal AO1 function 0~26
00
P10.23