EasyManua.ls Logo

Megmeet MV300 Series - Page 197

Default Icon
262 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
197
0: P14.02 digital reference
1: AI1 analog reference
2: AI2 analog reference
3: Reserved
4: Terminal PULSE reference
5: Serial port communication reference
0: AI1 analog feedback
1: AI2 analog feedback
2: Reserved
3: Terminal PULSE feedback
4: AI1 + AI2
5: AI1 – AI2
6: Min{AI1, AI2}
7: Max{AI1, AI2}
This value can be set via the operation panel or the serial port.
The PID command acceleration / deceleration is the soft start function to increase or decrease the PID
target value by the set acceleration / deceleration time.
The set time refers to the required time adding from 0.0% command to 100.0% command or the time
decreasing from 100.0% command to 0.0% command.
0: Positive action. When the reference increases, it shall be used when the motor is required to increase
its rotating speed.
1: Negative action. When the reference increases, it shall be used when the motor is required to
decrease its rotating speed.
The larger Kp is, the quicker response becomes, but too large Kp may easily cause oscillation and the
steady-sate error cannot be eliminated by using Kp control only.
The main functions of Ki lie in eliminating steady-sate deviation and making the feedback value
consistent with the target value. Too large Ki may easily cause overshoot and oscillation.
Differential
g
ain K
d
0.000~10.000
(
0.000
)
P14.07
Inte
g
ral
g
ain Ki 0.000~10.000
(
0.008
)
P14.06
Pro
p
ortional
g
ain K
p
0.000~10.000
(
0.500
)
P14.05
PID ad
j
ustment feature selectio
n
0~1
(
0
)
P14.04
PID command acceleration/deceleration time 0~3600.0s
(
0.0s
)
P14.03
PID di
g
ital reference -100.0~100.0%
(
0.0%
)
P14.02
Feedback channel selection 0~7
(
0
)
P14.01
Reference channel selection 0~5
(
0
)
P14.00

Table of Contents