203
Fig. 6-72 Setting of LED display parameter selection 2 when running
For the displayed terminal status, the terminal status adopts the defined value of the LED digital diode
through the multi-functional input terminal X1~X6 status (bit0~bit5 corresponding to X1~X6) and output
terminal Y1, Y2, RO1 (bit12~bit14 corresponding to Y1, Y2, RO1) to indicate the status of each function
terminal. For instance, when X1, X2 terminals are closed while other terminals are disconnected, it
indicates that the terminal state value is 03H.
Note: When the rotating speed or the line speed is displayed, it can be directly changed by pressing ∧
or
∨ key (no need to switch into the frequency state).
When 0 is selected for all the P16.00 and P16.01 BIT bits, the output frequency will be displayed by
default.
In the running parameter display state, the parameters for display can be switched in turn by pressing the
shift key 》.
Fig. 6-73 Setting of LED display parameter selection when stop
This parameter defines the parameters that LED can display when the drive is in stop state.
When 0 is selected for the BIT bit, it indicates that the parameter is not displayed.
When 1 is selected for the BIT bit, it indicates that the parameter is displayed.
Note: When the rotating speed or the line speed is displayed, it can be directly changed by pressing ∧
or
∨ key (no need to switch into the frequency state).
When 0 is selected for all the P16.02 BIT bits, the set frequency will be displayed by default.
LED dis
la
arameter selection when sto
0~FFFH
009
P16.02