33 
Type   Te rmi nal   Name  Function  Specification 
Power 
supply 
P24 
+24V power 
supply 
To provide +24V power for external load  Maximum output current: 200mA 
Common 
terminal 
PLC 
Multi-functional 
input common 
terminal 
Common end of Multi-functional input 
terminal  
(Short circuited with P24 upon delivery) 
Common terminal of X1~X6, PLC 
is interally isolated with P24 
COM 
+24V power 
common 
terminal 
2 common terminals in total, used 
together with other terminals 
COM is internally isolated with 
GND 
Relay 
output 
terminal 1 
TA 
Relay output 
It can be set as the digital output 
terminal with multiple functions. For details, 
please refer to the introduction to the 
functions of output terminals of P09.20 in 6.9 
“Digital input/output parameters” (Group 
P09) (common terminal: COM). 
TA-TB: normally closed; TA-TC: 
normally open 
Contact capacity:   
AC250V/2A
(
COS
=1
)
 
AC250V/1A
(
COS
=0.4
)
 
DC30V/1A 
For operating method, please refer 
to the description of P09. The 
over-voltage class for the input 
voltage of the relay output terminal 
is class II. 
TB 
TC 
 
Analog input terminal wiring   
1) When AI1 and AI2 terminals receive the single-end analog voltage or current input, with the voltage/current 
input selected via function code P10.00, the wiring mode is as shown in Fig. 3-6. 
10V~10V-
20mA~0
 
Fig. 3-6  Wiring diagram for AI1 and AI2 terminals