73
set
frequency
frequency
P02.12
Proportion
adjustment
coefficient of
set
frequency
Proportion
adjustment
coefficient
0.0%~200.0%
0.1 100.0
×
P02.13
Acceleration
time 1
Acceleration
time 1
0.0~3600.0
(Unit
adopts
that of
P11.01)
0.1
0.75~22:6S
30~45:20S
Others:30S
P02.14
Deceleratio
n time 1
Deceleration
time 1
0.0~3600.0
(Unit
adopts
that of
P11.01)
0.1
0.75~22:6S
30~45:20S
Others:30S
P02.15
Maximum
output
frequency
Maximum
output
frequency
MAX{50.00, upper limit frequency
P02.16}~ 3000.00Hz
0.01Hz 50.00 ×
P02.16
Upper limit
frequency
Upper limit
frequency
P02.17~P02.15 0.01Hz 50.00
P02.17
Lower limit
frequency
Lower limit
frequency
0.00~P02.16 0.01Hz 0.00
Group P03: Motor parameters
P03.00
Rated
power of
motor 1
Rated power 0.4~999.9KW 0.1 0 ×
P03.01
Rated
voltage of
motor 1
Rated
voltage
0~ rated voltage of drive (P98.04)
1 0 ×
P03.02
Rated
current of
motor 1
Rated
current
0.1~999.9A 0.1A
Depending
on model
×
P03.03
Rated
frequency of
motor 1
Rated
frequency
1.00.00~3000.0Hz 0.01Hz
Depending
on model
×
P03.04
Rated
rotating
speed of
motor 1
Rated
rotating
speed
0~60000rpm 1rpm 1440rpm ×
P03.05
Power
factor of
motor 1
Power factor
0.001~1.000
It shall be used when calculating
the motor parameters with the
nameplates
0.001
Depending
on model
×
P03.06
Stator
resistance
Stator
resistance
0.000~65.000 0.001
Depending
on model
×