EasyManua.ls Logo

Megmeet SPS-NE Series - Page 126

Default Icon
163 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
126
Function
code
Name
Index-
Sub-index
Value range
Min. unit
Default
value
Menu
mode
Cha
nge
Q
B
phases and three phases
1: Three phases
modulation
Thousands:
Low-frequency carrier
limit
0: Disabled
1: Enabled
P12.04
Current loop
gain selection
200C-05h
0: Manually select
1: Automatically calculate
(after auto-tuning)
1
0
×
×
P12.05
Current loop
proportional
gain
ACR-P
200C-06h
1 to 5000
1
1000
×
P12.06
Current loop
integral time
ACR-I
200C-07h
0.5 to 100.0 ms
0.1
8.0
×
P12.07
Power dip
ride-through
enable
200C-08h
0: Disabled
1: Enabled
1
0
×
×
P12.08
Frequency
decrease rate
during voltage
compensation
200C-09h
0.00 to 99.99 Hz/s
0.01
10.00
×
P12.09
Pre-excitation
time
200C-0Ah
0.0 to 10.0 s
0.1
0.0
×
×
P12.10
Minimum flux
setpoint
200C-0Bh
10% to 150%
1%
10%
×
P12.11
Field
weakening
adjustment
coefficient 1
200C-0Ch
0 to 10000
1
1000
×

Related product manuals