EasyManua.ls Logo

METREL TeraOhm 5kV Plus - Page 17

METREL TeraOhm 5kV Plus
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MI 3201 TeraOhm 5 kV Plus Measurements
17
After applying a high voltage to an insulator the electric dipoles distributed in the
insulator align themselves with the applied electrical field. This phenomenon is called
polarization. As the molecules polarize, a polarization (absorption) current lowers the
overall insulation resistance of the material.
The absorption current (I
PI
) typically collapses after a few minutes. If the overall
resistance of the material doesn’t increase, this means that other currents (e.g. surface
leakages) dominate the overall insulation resistance.
- PI is defined as the ratio of the measured resistances in two time slots. The most
typical ratio is 10 min value to 1 min value but this is not a rule.
- The test is typically performed at the same voltage as the insulation resistance test.
- If the one-minute insulation resistance is greater than 5000 M, then this
measurement may not be valid (new modern types of insulation).
- Oiled paper used in transformers or motors is a typical insulation material that
requires this test.
In general, insulators that are in good condition will show a “high” polarization index
while insulators that are damaged will not. Note that this rule is not always valid. Refer
to Metrel’s handbook Insulation Testing Techniques for more information.
General applicable values:
PI value Tested material status
1 to 1.5 Not acceptable (older types)
2 to 4 (typically 3) Considered as good insulation (older types)
4 (very high insulation resistance) Modern type of (good) insulation systems
Example for minimum acceptable values for motor insulation (IEEE 43):
Class A =1.5, Class B = 2.0, Class F =2.0, Class H =2.0.
DIELECTRIC DISCHARGE
The polarisation effect (described in “Polarisation Index”) causes a capacitance to form
(Cpi). Ideally this charge would dissipate immediately a voltage was removed from the
material. In practice, this is not the case.
In conjunction with the polarisation index (PI), Dielectic Discharge (DD) is another way
to check the quality and suitability of a insulation material. A material that discharges
quickly would provide a low value while a material that takes a long time to discharge
will provide a higher value (described in the table below, for more information see
section 5.6).
DD value Tested material status
> 4 bad
2 - 4 critical
< 2 good
Withstanding voltage test
Some standards allow the use of a DC voltage as an alternative to AC withstanding
voltage testing. For this purpose the test voltage has to be present across the insulation
under test for a specific time. The insulation material only passes if there is no
breakdown or flash over. Standards recommend that the test starts with a low voltage

Related product manuals