EasyManua.ls Logo

Metrohm 794 Basic Titrino - Page 47

Metrohm 794 Basic Titrino
198 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.7 Parameters, key <PARAM>
794 Basic Titrino
43
Relation between the stop criteria "time" and "drift"
The stop criterion "time", t(delay), means that the end point must be exceeded for a
certain period of time. In other words, after the last dosed increment, time t is allowed to
elapse before the titration is stopped. The size of this last increment depends on the
volume of the Exchange Unit used. With a 20 mL Exchange Unit, the smallest possible
increment is 2 µL. With a t(delay) = 5 s, the last 2 µL reagent must thus suffice for 5 s or
longer. This results in a drift of 2 µL/5 s = 24 µL/min (the drift can be less than 24
µL/min as it is not known whether the last increment would also suffice for 10 s). If you
have been working up to this point with a 20 mL Exchange Unit and a t(delay) = 5 s, you
can set a value of 24 µL/min as stop drift. The following table shows several values for
the maximum stop drift.
t(delay)
min.incr. (Exchange Unit)
5 s 10 s 20 s
0.5 µL (5 mL) 6 µL/min 3 µL/min 1.5 µL/min
1 µL (10 mL) 12 µL/min 6 µL/min 3 µL/min
2 µL (20 mL) 24 µL/min 12 µL/min 6 µL/min
5 µL (50 mL) 60 µL/min 30 µL/min 15 µL/min
Same t(delay) with a range of extremely small volume increments means different switch-
off points. In case the stop criterion "drift" is used, the stopping point remains the same.

Table of Contents

Related product manuals