8.6 Current Limit (01-20)
• In case the door encounters an obstruction during the Opening cycle, once the maximum Current limit is
reached for at least 2 seconds, the door Opening is then cancelled.
• Use the "UP" and "DOWN" buttons to select the desired "Current" limit strength.
• Activate the door to Open. During the Opening cycle, physically apply pressure to stall the door for at least 2
seconds.
• Check the force needed to reach the limit at which the door Opening is cancelled.
• Increase or Decrease this setting to achieve the correct strength needed.
•
Note: Setting of 10 is sufficient for most all applications.
8.7 Activation Time (01-60 seconds)
• This setting is the duration of the door Open cycle in seconds.
• The timer starts when the door starts to activate.
• Use the "UP" and "DOWN" buttons to select the desired "Opening" time.
8.8 Hold On Manual Open (No or 01-05 seconds)
• This setting is the length of time the door will be physically held Open, when the door is "Manually" pushed or
pulled open by a pedestrian.
• The door must be opened at least 60% of the door swing for this feature to activate.
• Use the "UP" and "DOWN" buttons to Enable or Disable this feature and set the timer value to keep open.
• Caution: Do not set timer for more than 1.0 seconds unless requested by the end user.
8.9 Electronic Door Stop (Yes/No)
• This feature is always Enabled even if you select Disabled.
8.10 Electric Lock (Yes/No)
• This setting is to Enable or disable the electric Lock/Strike through the Control unit.
• Select No when there is not an electric Lock.
• Use the "UP" and "DOWN" buttons to set the proper Electric Lock.
8.11 Electric Lock Delay (0.2-2.0 seconds)
• This setting is the length of time in seconds for the Delay between activating the Electric Lock and the Start of
the Opening cycle.
• Use the "UP" and "DOWN" buttons to Disable or Enable the electronic Delay/Output.
• Note: Setting of 0.2 seconds is sufficient for most applications.
8.12 Latch Position (2%-30%)
• This setting will adjust the door Latch position during the Closing cycle.
• Use the "UP" and "DOWN" buttons to set the starting point for the Latch position.
• Activate the door. During the Closing cycle, check the Latch starting position where the door begins to slow
down.
• Check this setting is correctly adjusted.
• If stack pressure is preventing the door from Fully Closing, set at 30% and activate the Power Close feature.