V6 VRF 50Hz
104
Midea V6 Series Service Manual
L7: Phase sequence error 2.15.10
L7 protection
Compressor wiring is loose
Reconnect cables based on
wiring diagram
An open circuit in the 3-phase U/V/W
of compressor terminals
Replace the compressor
Replace the inverter module
No
No
Yes
Yes
Disconnect the
power supply