V6 VRF 50Hz
85
Part 6 - Diagnosis and Troubleshooting
Procedure 2.8.5
E8
The ODU's address is not in the valid
range
1
Yes
Slave units addresses should be set from
1 to 3
No
Replace the outdoor main PCB
Notes:
1. The master unit address should be set as 0, slave units addresses should be set from 1 to 3, and the addresses should not be repeated within one system.