V6 VRF 50Hz
110
Midea V6 Series Service Manual
Procedure 2.16.5
Number of indoor units set on main PCB
not same as actual number of indoor
units
1
Change the setting on the PCB to be the
same as the actual number of indoor
units
Some indoor units are powered off
Power on all indoor units
After re-starting the ODUs and IDUs and
then waiting 2 minutes, an IDU displays
an E1 or FE error
2
Refer to indoor unit troubleshooting
guide. Resolving the indoor unit error
resolves the outdoor unit error
Two or more indoor units are assigned
the same address
3
Setting the indoor units’ addresses
uniquely resolves the error
Notes:
1. The number of indoor units can be set on switches EN3 and S12 on the main PCB.
2. Indoor unit error code E1 indicates a communication error between indoor and master unit. Indoor unit error code FE indicates that an indoor unit has not
been assigned an address.
3. Indoor unit addresses can be checked and manually assigned using indoor unit remote/wired controllers. Alternatively, indoor unit addresses can be
automatically assigned by the master outdoor unit.