EasyManuals Logo
Home>Midea>Air Conditioner>V6 Series

Midea V6 Series User Manual

Midea V6 Series
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #74 background imageLoading...
Page #74 background image
V6 VRF 50Hz
73
Part 6 - Diagnosis and Troubleshooting
Procedure 2.2.5
E0
ODU addresses on switch ENC1 are set
incorrectly
1
Yes
Set the ODU addresses correctly
No
Communication wires between ODUs are
not connected properly
2
Yes
Ensure the communication wires are
three-core shielded cable and are
connected properly
No
Wires between outdoor main PCB and
electric control box communication
terminals block are loose
Yes
Ensure the wires are connected properly
No
Replacing outdoor main PCB resolves the
error
No
Replace electric control box
communication terminals block
Notes:
1. The master unit address should be set as 0, slave units addresses should be set from 1 to 3, and the addresses should not be repeated within one system.
2. All the wires for H1, H2, E connections should be three-core shielded cable, the wiring should be connected according to polarity (H1 to H1, etc), the wiring
should not be open or short circuited.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea V6 Series and is the answer not in the manual?

Midea V6 Series Specifications

General IconGeneral
BrandMidea
ModelV6 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals