EasyManuals Logo
Home>Midea>Air Conditioner>V6 Series

Midea V6 Series User Manual

Midea V6 Series
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #112 background imageLoading...
Page #112 background image
V6 VRF 50Hz
111
Part 6 - Diagnosis and Troubleshooting
2.17 H8: High pressure sensor error
Digital display output 2.17.1
Description 2.17.2
High pressure sensor error.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.17.3
Trigger condition: Discharge pressure 0.3MPa.
Recover condition: Discharge pressure > 0.3MPa.
Reset method: Resume automatically.
Possible causes 2.17.4
Outdoor unit stop valves are closed.
Pressure sensor not connected properly or has malfunctioned.
Insufficient refrigerant.
Low pressure side blockage.
Poor evaporator heat exchange.
Main PCB damaged.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea V6 Series and is the answer not in the manual?

Midea V6 Series Specifications

General IconGeneral
BrandMidea
ModelV6 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals