V6 VRF 50Hz
84
Midea V6 Series Service Manual
2.8 E8: Outdoor unit address error
Digital display output 2.8.1
Description 2.8.2
Outdoor unit address error.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.8.3
Trigger condition: Outdoor unit address is set more than 3.
Recover condition: Outdoor unit addresses are set from 0 to 3.
Reset method: Manually restart.
Possible causes 2.8.4
Invalid outdoor unit address.
Main PCB damaged.