EasyManua.ls Logo

Midea V6 Series - 2.20 P2, H5: Suction pipe low pressure protection; 2.20.1 Digital display output; 2.20.2 Description; 2.20.3 Trigger; recover condition

Midea V6 Series
136 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
V6 VRF 50Hz
117
Part 6 - Diagnosis and Troubleshooting
2.20 P2, H5: Suction pipe low pressure protection
Digital display output 2.20.1
Description 2.20.2
Suction pipe low pressure protection. If the system has a 3-phase protector and the 3-phase protector is connected to
the low pressure switch, the system will display P2 protection when initially powered on, and P2 protection will
disappear once the system reaches a steady state.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.20.3
Trigger condition:
For P2 protection: Suction pressure 0.05MPa.
For H5 protection: P2 protection appears three times in 60 minutes.
Recover condition: Suction pressure 0.15MPa.
Reset method:
For P2 protection: Resume automatically.
For H5 protection: Manually restart.
Possible causes 2.20.4
Outdoor unit stop valves are closed.
Insufficient refrigerant.
Low pressure side blockage.
Poor evaporator heat exchange.
Main PCB damaged.

Table of Contents

Related product manuals