V6 VRF 50Hz
126
Midea V6 Series Service Manual
flowchart continued from previous page
The power supply is abnormal
Yes
Check the power supply equipment
No
Voltage between P and N on fan module
is abnormal
1
Yes
Replace AC filter board
No
Replacing the fan module resolves the
error
No
Replace outdoor main PCB
Notes:
1. The normal voltage between P and N on the fan module is 310V DC.
Figure 6-2.12: Fan module P N terminals