Analog Output
The HydroRanger I can be programmed to provide an analog output (P-6) of 0 or 4 - 20
mA, proportional or inverse span.
The 4 and 20 mA levels can be trimmed slightly via P-97 and P-98 respectively to
compensate for any offset between the HydroRanger I and the customer’s equipment.
The analog output feature may be turned OFF by setting P-6 = 0. The output and
alternate displays ( & P-92) will immediately drop to 0 mA after a new
measurement is processed. The output will remain disabled during simulation (P-76, 77
& 78). However, the test routine of P-92 and the trim parameters will remain active. If
P-60
≠
0, then the analog output will return to its programmed output after a new
measurement is processed.
If the analog output must be isolated, the optional mA isolator Model LIs-1 must be
mounted on the motherboard and wired per Figures 2 and 3. When using the isolator
the load adjust can be done via P-97 and 98 rather than via the load adjust
potentiometer as mentioned on the isolator instruction sheet, PL-293.
The current output responds in the following manner:
5
CURRENT
OUTPUT
Responds
to
if P-6=1 or 2,
reads 20 mA
when
if P-6=3 or 4,
reads 20 mA
when
differential
(if P-32 = 1 )or
level on xdcr 1
(if P-32 =2)
material
level
material
distance
head 1
(if P-50=1)
flow
(if P-50=2)
full
empty
empty
full
maximum
differential
or level
0
differential
or level
at max.
head
or flow
at 0
head
or flow
level
(if P-34=0)
or volume
(if P-34≠0)
full
empty
volume
full
empty
P2=1
LEVEL
P2=2
SPACE
P2=2
VOLUME
P2=5
OCM
P2=3
DLD.
P2=4
PUMP TOTAL
MODES
PL-399 5 – 10