SECTION VI
APPLICATIONS
Application Page
Simple Level 6 — 2
Pump Control 6 — 6
Pump Totalizer 6 — 12
Volume 6 — 16
Differential Level 6 — 24
OCM 6 — 28
Standpipes 6 — 44
This section highlights the most common applications for which the HydroRanger I
is designed. When calibrating, refer to the application which most suits your
requirements.
A practical example has been given to further illustrate the calibrating features used for
an application. In actual practice, however, the example may not cover all facets of the
particular application. Therefore, the user should become familiar with all of the
available parameters.
For ease of reference and programming, parameters have been organized into groups
relating to their function or application.
P-0 security
P-1 to P-7 general
P-8 to P-22 relays
P-23 to P-33 pump control
P-34 to P-39 volume and display conversion
P-40 to P-50 OCM
P-51 to P-59 OCM and pump totalizer
P-60 to P-67 custom calibration
P-68 to P-75 filters
P-76 to P-78 measurement and display
P-79 to P-88 echo processing and analysis
P-89 to P-98 testing
P-99 master reset
Parameter information can be obtained through Section VII, Parameter Description or
via Appendix III, Parameter Listing.
As the minimum distance from the transducer face to the target
is approx. 30 cm (1 ft.), near blanking (P-5) can be set up to a
minimum distance of 30 cm (1 ft.).
PL-399 6 – 1