SECTION VII
PARAMETER DESCRIPTION
NOTE:
(F) indicates the parameter’s factory setting, where applicable.
For reference only - factory set values may change with software revisions.
(V) indicates that parameter can be viewed only, not entered.
P-0 security
This parameter can be used to lock out the calibrator such that the content
of parameters P-1 through P-99 can not be changed. This however does
not prevent the parameters from being selected and viewed.
The calibrator is locked out if the content of P-0 is of any value other than
1954. P-0 can only be direct accessed.
content = 1954, calibrator functional (F)
1954, calibrator locked out
= – 1, pumps active during simulation
P-1 units of calibration and display
enter 1 = meters (F) 1* = calibrate in meters, display in %
2 = centimeters 2* = calibrate in centimeters, display in %
3 = feet 3* = calibrate in feet, display in %
4 = inches 4* = calibrate in inches, display in %
NOTE: For % display, entry must be made as and will be
displayed as “#P”
e.g. : press keypad switches and then , display will
appear as “3P”’
# *
3 *
PL-399 7 – 1