P-2 mode of measurement
enter 1 = liquid level
2 = space (F)
3 = differential level
4 = volume totalizer (pump totalizer)
5 = OCM (open channel measurement)
P-3 empty distance to transducer
enter desired amount (F=10.00 m)
P-4 span
- distance between full (high) and empty (low) levels
- max. level differential if DLD (P-2 = 3) is selected
- max. head if OCM (P-2 = 5) is selected
enter desired amount (F=10.00 m)
P-5 near blanking
enter distance required, in units as set in P-1. Note that entry must be
slightly larger than distance to end of standpipe or to far side of obstruc-
tion. (F=0.300 m)
P-6 milliamp output
enter 0 = off
1 = 0 to 20 mA
2 = 4 to 20 mA (F)
3 = 20 to 0 mA
4 = 20 to 4 mA
P-7 decimal point location
Sets the maximum number of digits after the decimal. The number of digits
after the decimal will automatically reduce to avoid display overflow.
enter 0 = no digits after decimal
1 = one digit after decimal
2 = two digits after decimal (F)
3 = three digits after decimal
P-8 relay 1 function
Refer to Section V, Relays.
enter desired option (F=0)
P-9/10 relay 1 - ON/OFF setpoints
enter level in units as selected in P-1 or °C (F=----)
PL-399 7 – 2