Milltronics HydroRanger I - Example 6 A

Milltronics HydroRanger I
104 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
P-5 enter 1, near blanking distance, minimum allowable
P-39 enter option 4, display flowrate in units per day
P-40 enter option 1, primary measuring device - exponential
P-41 enter option 4, flowrate time units - per day
P-42 enter 1.53, exponent from manufacturers specs. for 9" Parshall Flume
P-46 enter 4112, max. flow in thousand gal./day
P-49 enter option 3, flowrate decimal point display max. 3 digits after decimal
P-52 enter option 0, totalizer convert display total is divided by 1 before being
displayed or 1 count per thousand gallons
P-53 enter option 2, totalizer decimal point display 2 digits after decimal or
resolution equals 1/100th of a count
P-68 enter 32.81, fill damping 32.81 ft/min As the head would fluctuate over a
period of hours, damping requirements would be fairly low.
Typically, the factory set damping of 32.81 can be used.
P-69 enter 32.81, empty damping - same as fill damping
Example 6a
(Auto Zero)
Further to Example 6, the following is required:
alarms at 10% overflow (approx. = 1.8 ft) and 0 head
in the event of loss of echo, the HydroRanger I is to go into low alarm after
45 sec.
head to read to 1 decimal place
sampler contact every hour
head under 1" (40 thousand gal./day) not be totalized
4-20 mA output to respond to flow