relays » 5 multi-purpose relays (for alarms, pump control, ...)
» 1 Form ’C’ SPDT contact per relay, rated
5 A at 220 V AC non-inductive
» adjustable deadband
NOTE:
All relays are certified for use in equipment where the short circuit
capacity of the circuits in which they are connected is limited by fuses
having ratings not exceeding the rating of the relays.
Enclosure » CSA type 4 (NEMA 4/ IP 65 style)
» 160 mm W x 240 mm H x 82 mm D
(6.3" W x 9.5" H x 3.2" D)
» polycarbonate
Weight » 1.8 Kg (4 lb)
Programmer
Enclosure » general purpose
» 67 mm W x 100 mm H x 25 mm D
(2.6" W x 4" H x 1" D)
» ABS plastic
Operating Temp. » -20 to 50 °C
(-5 to 122 °F)
Battery » 9 V (ANSI/NEDA 1604, PP3 or equivalent)
Transducer
Model » ST-H with integral temperature sensor
Construction » 1" NPT conduit thread with standard 10 m (33 ft)
of neoprene jacketed cable.
» 2" NPT, 2" BSP or PF2 mounting thread
» Tefzel
®
encapsulated
Operating Temperature » -40 to 73 °C (-40 to 165 °F)
Pressure (vessel) » 200 kPa (2 bar or 30 psi) max.
Beam Angle » 12°
PL-399 2 – 2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Milltronics HydroRanger I and is the answer not in the manual?

Milltronics HydroRanger I Specifications

General IconGeneral
BrandMilltronics
ModelHydroRanger I
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals