Example 3
Further to example 2 it is required that the volume pumped be totalized. A daily flow
total of 1,200 cubic meters is expected and a contact closure is required every 10 cu.
m. The full level of the well is equal to 42 cu. m. The following parameters should be
set.
select:
P-2 enter option 4, volume totalizer
P-17 enter option 11, relay 4 - remote totalizer contact
P-33 enter option 1, estimated inflow volume is added to pumped volume
P-37 enter 14, convert display (x14)
42/3 = 14
P-39 enter option 2, display low total
P-52 enter 1, totalizer convert display, totalized volume will read as tens of
cubic meters or 1 count per 10 cubic meters.
P-53 enter option 0, totalizer decimal point no decimal digits or resolution
equals 100% of a count
P-54 press
enter 0, totalizer preset value, arbitrarily chosen
P-55 press
enter 0, totalizer preset value arbitrarily chosen
P-56 enter 1, totalizer contact control - closure every 10 cu. m
press
to re-enter run mode.
CLR
CLR
RUN
CAL
PL-399 6 15