Parameters P-34 through P-39 are used for volume and display conversion.
P-34 tank shape for volumetric conversion
enter 0 = non volume - linear level measurement (F)
1 = flat bottom
2 = conic or pyramidic bottom
3 = parabolic bottom
4 = half sphere bottom
5 = flat slope bottom
6 = horizontal cylinder, flat ends
7 = horizontal cylinder, parabolic ends
8 = sphere
9 = universal level vs volume
(refer to Section VI, Volume Application)
if P-34
≠
0, reading will be in percent of P-04. For volumetric reading, set
conversion factoring into P-37
P-35 tank dimension A
the height of the bottom section of tank shapes 2, 3, 4, 5 or the length
of one end section in tank shape 7 (
not required
for other tank shapes).
enter “dimension A”, in units selected per P-1 (F=0.000)
P4
P4
P4
P4
P4
1 = Flat Bottom
2 = Conic or Pyramidic Bottom
6 = Horizontal Cylinder, flat
ends
8 = Sphere
5 = Flat Sloped Bottom
7 = Horizontal Cylinder,
parabolic ends
"
3 = Parabolic Bottom
or
4 = Half Sphere
A
A
A
L
A
P4
P4
PL-399 7 – 6