alternates display to show either the parameter number or parameter
contents
enters display as contents of selected parameter
Parameter Entry
Initial Start-Up
NOTE All entries are made via the calibrator keypad. All calibrators are
interchangeable, thus any calibrator can be used in conjunction with any
HydroRanger I. The term “key” refers to any keypad switch of the
calibrator.
1)Apply power to the HydroRanger I and place the calibrator in its front cover
recess
run will be momentarily displayed and then a distance reading corresponding to
the parameter factory settings will appear. This is a space or distance
reading of up to approximately 12 m.
If ’CAbL’/’LOE’ is alternately displayed, an open, short circuited or reversed
polarity transducer connection is being indicated.
If LOE is displayed rather than a continuous numeric reading the actual
material distance may be beyond 12 m. Proceed with the calibration and if
LOE persists, consult the troubleshooting guide, Section VIII.
2)press
CAL will be displayed
3)press
P-1 will appear
NOTE: the CAL display will revert to the run mode if is not pressed within a
minute and a half of initially pressing the CAL switch.
The user may now program the HydroRanger I.
ALT
DSP
ENTER
RUN
CAL
*
*
PL-399 4 – 3