The ‘ running hours ’ and ‘ starts ’ may also be viewed in the run mode.
Refer to Application \ Pump Control Application.
P-29 pump run-on interval
the cyclical period in hours, in which a pump run-on duration may occur.
The initial interval begins upon return to the run mode or resumption of
power to the HydroRanger I. Subsequent intervals begin at the end of the
previous interval. Intervals end after the time entered has expired or when
the power or run mode is interrupted.
enter interval in hours (F=0.000)
P-30 pump run-on duration
the amount of time which the lead pump will continue pumping after it has
reached its OFF setpoint.
enter duration is seconds (F=0)
P-31 spare
P-32 DLD milliamp output
when operating in the DLD mode, the milliamp output can be set to
correspond either to the differential or to the level under transducer #1
(refer to Figure 3)
enter 1 = differential (F)
2 = level
P-33 inflow/discharge totalling
refer to Section V, Pump Totalizer Application
enter 1 = estimated inflow or discharge volume is added to the
pumped volume total (F)
2 = estimated inflow or discharge volume is omitted from
the pumped volume total