P-11 relay 2 function
Refer to Section V, Relays.
enter desired option (F=0)
P-12/13 relay 2 - ON/OFF setpoints
enter level in units as selected in P-1 or °C (F=----)
P-14 relay 3 function
Refer to Section V, Relays.
enter desired option (F=0)
P-15/16 relay 3 - ON/OFF setpoints
enter level in units as selected in P-1 or °C (F=----)
P-17 relay 4 function
Refer to Section V, Relays.
enter desired option (F=0)
P-18/19 relay 4 - ON/OFF setpoints
enter level in units as selected in P-1 or °C (F=----)
P-20 relay 5 function
Refer to Section V, Relays.
enter desired option (F=0)
P-21/22 relay 5 - ON/OFF setpoints
enter level in units as selected in P-1 or °C (F=----)
Parameters P-23 through P-33 are used specifically for pump applications. Refer
to Section VI.
P-23 submersible transducer
enter 0 = normal ST-series transducer (F)
1 = submersible transducer
P-24 relay 1 pump log *
PL-399 7 – 3