P-14 enter option “5”, relay 3 - rate of change function
P-15 enter “-1”, relay 3 - alarm ON
P-16 enter “-0.9”, relay 3 - alarm OFF
P-37 enter “1”, convert display (x1)
P-68 enter “1”, max. fill damping 1 ft/min
P-69 enter “1”, max. empty damping 1 ft/min
P-74 enter option “3”, fail-safe hold
P-75 enter “2”, fail-safe timer - 2 min.
press:
to re-enter run mode
RUN
CAL
PL-399 6 – 4