EasyManua.ls Logo

Milltronics HydroRanger I - Page 40

Milltronics HydroRanger I
104 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
advance to:
P-2 enter option "1", material level
P-3 enter "6.5", empty distance to transducer
P-4 enter "6", span
P-5 enter ".5" near blanking distance
P-34 enter option "9" universal level vs. volume
press display will show
or enter
*H-1
ALT. DISP. ----
00
ENTER 0.000
H-2
----
1 1
ENTER 1.000
H-3
----
3 3
ENTER 3.000
H-4
----
4 4
ENTER 4.000
H-5
----
6 6
ENTER 6.000
* F-5
----
ALT. DISP. F-5
1 F-1
ALT. DISP. ----
PL-399 6 20