P-51 OCM simulation
press , display will show previous flow
enter head in units programmed, display will show head
press , display will show corresponding flow
Parameters P-52 through P-59 are used specifically for OCM and pump
totalizer applications. Refer to Section VI.
P-52 totalizer display factor
totalizer display of flow or volume pumped is factored by a power of 10
to determine the count per flow. The factor is selected as follows:
enter -3 = multiply by 1000
-2 = 100
-1 = 10
0 = divide by 1 (F)
1 = 10
2 = 100
3 = 1,000
4 = 10,000
5 = 100,000
6 = 1,000,000
7 = 10,000,000
e.g. present flow rate is 450 gal./sec
if P-52 = 0, totalizer is incremented at a rate of 1 count per gallon
if P-52 = 3, totalizer is incremented at a rate of 1 count per thousand gal-
lons
P-53 totalizer decimal point location
sets the number of digits after the decimal point for the low total only. The
decimal point will not float.
enter 0 = no digit after decimal
1 = one digit after decimal
2 = two digits after decimal (F)
3 = three digits after decimal
P-54 low total
this parameter will display the 4 lowest digits of the 8 digit totalizer used
in pump totalizer or OCM applications. The parameter will also allow the
display to be reset to any value. (F=00.00)