press , the HydroRanger I will take a measurement and display the
level in the linear units chosen regardless if percent, volume or convert
display is used. Press MEAS at least 5 times and insure that a stable
reading is being obtained
enter the actual physical measurement or level
press , the HydroRanger I will now calculate the correct
measurement offset to be used in future measurements and automatically
enter it into P-62.
P-61 empty calibration
this provides sound velocity compensation on an empty tank. This is
required on a volume application where the atmosphere in the tank is
other than air or the atmospheric temperature is constant but other than
20°C and no temperature sensor is being used. (F=-----)
empty tank as much as permissible. Leave filled with normal vapour and at
normal operating temperature. Refer to Figure 7.
press , the HydroRanger I will take a measurement and display the
level in the linear units chosen regardless if percent, volume or convert
display is used. Press MEAS at least 5 times and insure that a stable
reading is being obtained.
enter the actual physical measurement or level
press , the HydroRanger I will now calculate the correct sound
velocity to be used in future measurements and automatically enters it into
P-63 and P-64.
P-62 measurement offset
this displays the measurement offset; used in conjunction with a full tank
calibration, P-60, or an offset value may be entered directly. The offset is
added to the ultrasonic measurement such that its effect will be carried
through the reading (P-39, P-76 or ) mA output and relay setpoints.
(F=0.000)
MEAS
ENTER
MEAS
ENTER
*
PL-399 7 12