EasyManua.ls Logo

Milltronics miniranger plus - Pump Control in Wet Wells

Milltronics miniranger plus
77 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 46 MiniRanger Plus 7ML19981CJ01
Applications
Pump Control Application
The basic difference between a simple level application and a pump control
application is that the relays assigned to pump function (P111) are normally
de-energized (off) and energized when required to run the pump. In the
program mode, pump relays are held de-energized.
Pumps can be programmed to work independently or in lead/lag fashion.
Refer to 36.
In applications where flooding is possible, a submersible transducer should
be used. The submersible transducer's air cavity insures that a high level
reading is maintained rather than establishing a loss of echo condition, when
the liquid level reaches the transducer. When using a submersible
transducer, set P802 = 1.
Example
The application is to control the level in a wet well. It is required that the level
be displayed in centimetres. The transducer is mounted at 3.6 m from the
bottom and is equipped with a submergence coupling as there is possibility
of flooding in the well. Two pumps are to be controlled by the MiniRanger
Plus in lead / lag fashion. The first pump to start at 1 m and the second
pump to start at 2 m. Both pumps are to stop at 0.25 m. The maximum
estimated filling rate is 1 m/min. In the event of a loss of echo, a fail-safe low
after 6 sec is required to protect the pumps from running dry.
P006
3.6m
P007
3.0m
relay 2,
pump on
P112-2, 1m
relay 1 & 2,
pumps off
P113-1&2, 0.25m
relay 1,
pump on
P112-1, 2m

Related product manuals