Page 60 MiniRanger Plus 7ML19981CJ01
Parameter Description
Example
To reference the displayed level to sea level, enter the distance in Units
(P005), between Empty (P006) and sea level. (Enter a negative value if
Empty is below sea level.)
Values
-999 to 9999
Preset: 0.000
P070 Fail-Safe Timer
The amount of time delay, in minutes, before going into fail-safe mode.
Note:
Disabled for h.I.s. operation (P001 = 4)
P071 Fail-Safe Material Level
Selects the default measurement in the event that the fail-safe timer expires.
entry :
1 = high; maximum span value
2 = low; minimum span value
3 = hold; hold current value
Note:
Disabled for h.I.s. operation (P001 = 4)
P006
reservoir
P007
P062
sea level