24 Calibration
DECELERATION (DECEL)
The DECEL setting determines the time the motor takes to ramp
to a lower speed. See Specifications on page 1 for approximate
deceleration times. DECEL is factory set for the fastest
deceleration time (full CCW).
To set the deceleration time:
1. Set the speed adjust potentiometer full CW. The motor should
run at maximum speed.
2. Turn the speed adjust potentiometer full CCW and measure the
time it takes the motor to go from maximum to minimum
speed.
3. If the time measured in step 2 is not the desired deceleration
time, turn the DECEL trimpot CW for a slower deceleration
time, or CCW for a faster deceleration time. Repeat steps 1
through 3 until the deceleration time is correct.