EasyManuals Logo

Mircom Fire-Link NMC-100 Series User Manual

Mircom Fire-Link NMC-100 Series
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
Installation and Programming Manual
Mircom Technologies Inc All Rights Reserved LT-1034 Rev.1
Page 12 of 54
2.3 Slave Mode (Preferred method in Canada)
In Slave Mode, the NMC is wired into a spare FACP signal circuit. When an alarm condition occurs, the reversal
of the bell output polarity will cause the NMC to alarm as well. When the FACP Signal Circuits are silenced, the
NMC Bell Output Relay will reset to ‘normal state’ causing the NMC to silence the ISDs and return from alarm
state to normal state. If the FACP re-alarms, this will cause the NMC to re-alarm as well. Connect the Signal
Circuit wiring of the FACP to the NMC Bell Output Relay IN+ and IN- terminals, observing polarity. Wire the FACP
signal circuit end of line resister to the NMC OUT+ and OUT- terminals.
Figure 2 below shows the wiring
schematic.
Figure 2- NMC- Slave Unit Wiring
2.4 Alarm Zones
See Figure 3 below for wiring schematic. NOTE: The resettable power terminal has an output voltage range
of 10.70VDC to 20.27VDC.
Figure 3- 4 Wire Smoke Detector

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mircom Fire-Link NMC-100 Series and is the answer not in the manual?

Mircom Fire-Link NMC-100 Series Specifications

General IconGeneral
BrandMircom
ModelFire-Link NMC-100 Series
CategorySecurity System
LanguageEnglish

Related product manuals