496
28 FUNCTIONS
28.14 External Input/Output Forced On/Off Function
Forced on/off timing
The following table lists the timing to reflect forced on/off registration information to the input/output devices or external
outputs.
*1 At input/output refresh execution where input/output refresh is registered for each program, and for interrupt programs.
*2 Forced on/off is reflected only to output devices. (Since refresh to external outputs is not executed.)
*3 Forced on/off is reflected only to input devices on the standby system. (Since refresh from the CPU module to link devices is not
executed.)
*4 Whether external outputs to the standby system are reflected or not differs depending on the standby system output setting. ( Page
495 Reflection to external outputs of the standby system)
Input/output for which forced on/off
can be set
Reflection timing for the input devices Reflection timing for the output devices or
external outputs
*4
Input/output of the modules mounted on the
base unit
END processing (at input refresh)
At COM instruction execution (at input refresh)
At instruction execution using the direct access
input (DX) (LD, LDI, AND, ANI, OR, ORI, LDP,
LDF, ANDP, ANDF, ORP, ORF, LDPI, LDFI,
ANDPI, ANDFI, ORPI, ORFI)
At RFS instruction execution
At execution of instructions used in the interrupt
by the system (UDCNT2)
At program execution
*1
At reflection of the tracking receive data to devices
END processing (at output refresh)
At COM instruction execution (at output refresh)
At instruction execution using the direct access
output (DY) (OUT, SET, DELTA(P), RST, PLS,
PLF, FF, MC, SFT(P))
*1
At RFS instruction execution
At program execution
*1
At reflection of the tracking receive data to
devices
*2
Input/output of the CPU module assigned to LX
and LY of the CC-Link IE Controller Network
module
*3
END processing (at link refresh of the CC-Link IE Controller Network module)
At COM instruction execution (at link refresh of the CC-Link IE Controller Network module)
At ZCOM instruction execution (at link refresh of the CC-Link IE Controller Network module)
Input/output of the CPU module assigned to RX
and RY of the CC-Link IE Field Network
module
*3
END processing (at link refresh)
At COM instruction execution (at link refresh)
At ZCOM instruction execution (at link refresh)